Operation mode of Disconnector

PostTime: 2022/5/18 14:35:02   Views: 3912

The disconnector can be divided into manual disconnector and electric disconnector according to the operation mode;

Manual disconnector:

After receiving the switching order, the operator and supervisor shall jointly confirm the position and opening and closing status of the disconnector.

The operator opens the lock of the disconnector, pulls out the switch pin and inserts the operating rod.

Quickly pull the disconnector operating rod clockwise or counterclockwise to open and close the switch in place. The operation shall be accurate and rapid, the opening and closing shall be in place at one time, and there shall be no stopover and impact in the middle.

The disconnecting switch operated by the main switch blade and the grounding switch blade respectively must be opened and closed in the following order: when closing, the grounding switch blade shall be disconnected first and then the main switch blade shall be closed; When disconnecting, disconnect the main knife switch first and then close the grounding knife switch.

After the operation, confirm the opening and closing status of the disconnector.

Electric disconnector:

Operate on the protection measurement and control panel

Turn the "remote / local" change-over switch of OCS disconnector of protection measurement and control panel to the proper position.

Press the disconnecting and closing buttons of the catenary to start the operation. Press the red button to switch on, and the red button is on; Press the green button to open the brake, and the green light of the button is on.

After the operation, confirm that the indication of the indicator is consistent with the state of the disconnector.

Electric operation on mechanism box body

Open the mechanism box of OCS disconnector and turn the operation change-over switch to LOC position (REM is "remote" position, LOC is "local" position and man is "manual"

Operate on the opening and closing buttons. The red button is closing and the green button is opening. After the operation, check and confirm that the opening and closing indicator of the corresponding feeder protection measurement and control panel is consistent with the state of the circuit breaker.

Manual operation of the mechanism box body

Open the mechanism box of OCS disconnector and turn the operation change-over switch to man position.

If the control circuit has power, you can directly pull down the baffle of the hand hole on the right side of the mechanism box, insert the "operation handle" into the "hand hole", and open and close according to the mark.

If there is no control power supply, insert a small cross screwdriver into the small hole at the upper left side of the manual baffle, then pull down the manual baffle and insert the "operation handle" into the "manual hole" for operation. Clockwise is closing and counterclockwise is opening.

After the operation, confirm the opening and closing status of the disconnector.

The switch shall be locked in time and personnel shall be evacuated.

During operation, wear insulating boots, insulating gloves and safety helmet.

It is strictly prohibited to switch the disconnector on load.

The transmission mechanism of each disconnector must be locked.

Back: End
Next: Three types and differences of vacuum circuit breaker

Links: Tianlong Electrical

日韩人人弄人人爱视频| 日韩欧美永久免费aⅴ在线| 国产黑色丝袜不卡码无码| 国模私拍花絮在线| 欧美一区二区三区+黄色| 欧美婷婷成人在线| 成人一级A片AV综合导航| av一二三四区在线| 日韩最新免费黄色视频| 我想看一级黄色片日皮的| 日产女孩中文字幕在线免费观看| 俄罗斯熟女AV在线| 能看的免费的A片| 精品国产911区二区三区| 色色另类综合日韩| Av女区在线免费观看网站| 三级片资源站国产一级性交片| 国产艾薇在线网站| 人人操人人妻人人射| 人人妻人人爱人人操| 欧美黄色一级片与日本美女| 亚洲激情Av国产精品爱在线| 日韩综合AV亚洲啪啪爱视频 | 国产性爱网址视频| 97在在线视频亚洲好好日天堂| 亚洲看片在线五月丁香色色| 蜜桃丰满熟妇av无码区不卡| 黄片视频看看丝袜五月| 911一区二区三区| 日av不卡在线观看字幕| 亚洲歐洲日韓av| 无码免费不卡三级片| α片在线视频亚洲日韩男女| 日韩无码精品推荐| 亚洲成人电影精品| 亚洲视频色情在线| 国产自一拍99精品| 亚洲色情网站大全免费黄色片| 人妻精品黄网在线| 青青青青草成人视视频| 欧美认成不卡在线|